10,000 Watt Diesel Power Generator

Small, Simple and Effective Diesel Industrial Generator

Water Cooled Diesel Generator

 

Model AGI10X
$4,499.00 - Buy Now

Take the enclosure off our very popular 10,000 watt silent diesel generator and you have this less expensive version. This generator uses the same engine, alternator, wiring methods, belly fuel tank and control. Since this generator is no longer weatherproof, many install it under some shelter or place it in a well ventilated garage.

Many other generators this size do not come with a main circuit breaker, battery, belly fuel tank and digital engine controller; this one does. When you receive it, there is very little setup required. Add coolant, lube oil and fuel. Next connect the battery. You can use the included muffler or extend the existing one to vent out of a roof or wall if you wish. You have many installation options.

Many people find portable generators can't produce the extra power they need. Larger standby generators are more expensive than this smaller size one. So this tractor engine driven diesel generator is the next best thing. Slower turning liquid cooled engines are designed to last ten times longer making them a good investment. Unlike portable air cooled engines, these engines can run full time.


Highlights

  • Built-in belly fuel tank. Connecting to a larger fuel tank of your own is easy and is often used to extend running time.
  • Higher quality generator head that is maintenance free and brush-less. You are insured the highest quality possible since it is both CSA and UL approved / certified.
  • 120 volt and 240 volt single phase only
  • Automatic Voltage Regulator - User Adjustable Voltage setting.
  • Includes Muffler
  • Digital Generator Controller
  • Powerful 3 Cylinder 1800 RPM Engine built to last over 10,000 hours.
  • Battery
  • EPA Tier 4 Approved
  • Cold Start Preheater
  • Can easily be connected to optional Automatic Transfer Switch

 

Installed Glow Plugs

Glow Plugs make starting diesel engines easier in cold weather. Glow plugs are heaters that glow red hot in the intake manifold. Air entering the combustion chamber is heated as it passes through and this aids in fuel atomization and combustion. This generator has glow plugs installed.

Fuel Tank

Built into the base of this generator is a fuel tank. It holds enough fuel for about 24 hours of operation.
The generator panel has an analog gauge showing you how much fuel is left. Also, there is a float type fuel gauge built into the fuel cap itself. Connecting to a larger fuel tank is easy since the fuel pump can work with the fuel supply above or below the pump.

Generator Control Panel

Automatic Voltage Regulator

This generator uses an Auotmatic Voltage Regulator (AVR). Output voltage is regulated to +- 1%. The AVR response time is 20 ms resulting in a very stable output during changing load conditions. On this generator panel, you can also easily change the output voltage. Increase or decrease it as you see fit. The adjustment sell the AVR what voltage it should maintain. This is helpful when you wish to overcome voltage loss in long length of cables back to the house or wish to fine tune it for any reason.

Diesel Generator 10,000 Watts

 

Generator Controller

This generator uses a digital engine controller. The controller is used for automatic up and shut down the generator. Start up can be either by a push of a button or by a switch you can connect for remote use. You can even connect to most Automatic Transfer Switches. The controller monitors the engines temperature, speed and, oil pressure. Also, monitored is the battery charging, generator output voltage and frequency. When the generator is run unattended it will monitor for a fault in one of those monitored inputs and shut down to help prevent any damage. The built in hour meter also help you tell when it is time to change the oil.

SmartGen Generator Controller

 

General Specifications
Generator Model Number AGI10S - 10,000 Watts
No Enclosure 39" x 30" x 39" - actual size 49" x 40" x 39" - with crate 950 lb
Enclosed Silenced Type 62" x 32" x 39" - actual size 63" x 34" x 49' - with crate 1250 lbs
Built in fuel tank 70L / 18.5 gallons
Starting System Fully Automatic via controller
Generator Controller SmartGen HGM1770
Electrical Specifications
Alternator Model Dingol CSA Approved Stamford Type Brushless
Alternator Peak Power 10,000 Watts
Alternator Continuous Power 9,000 Watts
Voltage 120 & 240 Volts (adjustable)
Regulator Type Automatic Voltage Regulator
Insulation Class H
Protection Class IP22
Efficiency 92.8%
Adjustable Voltage Range 6%
Steady Voltage Regulation 1%
Rated Speed / Frequency 1800 rpm / 60 Hz 1500 rpm / 50 hz
Phase Singe Phase
Power Factor 1.0
Rated Alternator Output Current 41.7 Amps (240 Volts) / 83.3 Amps (120 Volts)
Engine Specifications
Engine Model KM385
Engine Type Water Cooled, 4 Cycle, Direct Injection
Certifications 2010 EPA Tier 4 Approved
Fuel Type Low or Ultra Low Sulfer Diesel
Expected engine life before rebuild Over 10,000 Hours
Maximum Altitude 5000 feet
Bore (mm) x Stroke (mm) 85 mm x 85 mm
Number Of Cylinders 3
Displacement 1.532L
Compression Ratio 21.5
Rated Power Speed 1800 RPM / 60 Hz or 1500 RPM / 50 Hz
Rated Power 17 kw / 22.8 HP
Lowest Fuel Consumption g/kW.Hr 265
Lowest Oil Consumption <2.72 g / kW.Hr
Lube Oil Diesel Motor Oil 15w40 (synthetic recommended)
Oil Volume 3.5L / 3.7 qt.
Intake Valve Clearance (cool) 0.20-0.25mm
Exhaust Valve Clearance (cool) 0.25-0.30mm
Fuel Filter CX0706 (replace every 400 hours)
Oil Filter Baldwin WB178 (replace every 200 hours / 3 months)
Speed Governor Mechanical

Connecting this generator to your home.

The generator panel has a 30 amp 120/240 volt L14-30 type outlet installed in it. If you own an existing portable generator, you will like being able to quickly switch to this one. All you do is plug into it as you would with any other generator. There is even a main circuit breaker to help protect the generator head from overload. Larger terminals inside are for connecting heavier cable too that you would then wire to your home, transfer switch or existing panel.

Reviews

Generator Reviews
How did we do? What do you think about us? It's easy to rate or review Aurora Generators.  Why not take a moment to see what others have to say or, add your own comment.

You can also start a discussion with others on our Discussion Forum

KM385 Parts

KM385 Spare Parts