12 kw Diesel Standby Generator
Brushless Alternator with Automatic Voltage Regulator
Includes Muffler, Battery, Belly Fuel Tank and Digital Generator Controller
$3,999.00
This generator was developed for those who need dependable backup power without paying more expensive enclosures. It supplies a little less power then traditional enclosed units but far better for supplying backup power then a portable generator. The engine is the same YD385 model used in farm tractors around the world. You can expect over 10,000 hours of use out of this water cooled 1800 RPM engine. Many people install then in a garage, shed or beneath an overhang.
Highlights
- Built-in belly fuel tank
- Maintenance Free Brushless Alternator
- Automatic Voltage Regulator
- Includes Muffler
- Digital Generator Controller
- Battery
- EPA Approved
- Installed Cold Start Preheater
Alternator / Generator
- Single Phase 120 and 240 volts
- Can be used for either 50 Hz or 60 Hz use
- Brushless Type
- Uses an Automatic Voltage Regulator
Generator Controller
This generator includes The Model 170 Automatic Engine Control Module. The module is used to automatically start and stop the engine, indicating the operational status and fault conditions, automatically shutting down the engine and indicating the engine failure by LED on the front panel.
Operation of the module is via a three position key switch mounted on the front panel with OFF, START and AUTO positions. In the OFF position the output are de-energized.
Manual Operation:
Once the Start button is pressed and held, the engine fuel system is energized. The Crank output is then energized and the starter motor operated, disengaging automatically when the engine fires or when the “Start’ button is released. The protection hold-off timer is then initiated.
Automatic Operation:
When used in Automatic mode the controller will monitor for the following conditions and if a failure is detected it will shut down the engine:
- Low Oil Pressure
- High Engine Temperature
- Auxiliary Shutdown
- Battery Charge Failure Warning
- Over speed (dirived from alternator frequency Hz. measurment Can be set to 50 or 60 Hz.)
This will remove the fuel supply from the engine and bring it to rest. Each alarm has its own LED indicator and once activated no further alarm conditions will be accepted. The alarm output and relevant LED will remain active until the unit is reset by turning the switch to the off position.
During engine cranking and for a short time afterwards the protection hold-off timer (10 seconds) is active and the relevant alarm inputs are inhibited. This enables the engine to start and achieve normal running conditions. Once the timer has expired the inputs are enabled providing normal protection from the module.
| Generator Model Number | AGI12KW |
| Manufacture | Aurora |
| Rated Speed / Frequency | 1800 rpm / 60 Hz 1500 rpm / 50 hz |
| Prime Output Power | 10,000 Watts |
| Standby Output Power | 12,000 Watts / 14.4 kVA |
| Voltage / Phase / Wire | 120 & 240 Volt Singe Phase |
| Power Factor | 0.8 (lag) |
| Rated Alternator Output Current | 50 Amps (240 Volts)100 Amps (120 Volts) |
| Dimension | 1450 mm x 650 mm x 1000 mm 4.8’ x 2.1’ x 3.3’ |
| Wooden Crate Dimensions | 1500 mm x 700 mm x 1100 mm 4.9’ x 2.3’ x 3.6’ |
| Net Weight | 450 KG | 992 lbs |
| Diesel Engine Model | Y385G |
| Engine Character | 3 Cylinder Water Cooled, 4-cycle, Direct Injection |
| Altitude | Not indented for use above 3000 feet |
| Bore (mm) x Stroke (mm) | 85 mm x 90 mm |
| Fuel Consumption | g/kw.h 247 |
| Included Belly Tank | 50 L | 13.2 Gallon |
| Lube Oil Capacity | |
| Cooling Water Capacity | |
| Start Model | Electric |
| Speed Governor | Mechanical |
| Alternator Type | Leroy Somer Brushless Single Phase |
| Insulation Class | F |
| Protection Class | IP22 |
| Efficiency | 92.8% |
| Voltage Adjust Range | 6% |
| Steady Voltage Regulation | 1% |
| Voltage Regulation | Automatic Voltage Regulator |